Stage 2 · Framing & ledger flashing
Framing & flashing: the chapter about rot
More decks collapse from the ledger joint than from any other detail, and more houses are damaged by decks than decks are damaged by houses. Both facts trace to the same few inches of wall where deck meets house — and to whether water was given a way out.
The ledger joint, done properly
The sequence that works: house wrap and flashing integrated so water running down the wall is kicked out over the ledger, never behind it; the ledger fastened with ½-inch hot-dip galvanized or stainless bolts/lags in the pattern the code table specifies for the joist span — never with nails, never with deck screws; a self-adhering membrane over the ledger top; and a gap or spacer detail where local practice requires drainage behind the board. Failure modes, in the order they are usually found: flashing omitted entirely; flashing installed but lapped backwards so it funnels water in; ledger bolted over siding, crushing it and holding a permanent moisture sandwich; fasteners corroded to wire thickness by modern preservatives (see below). A deck that pulls away from a house almost always shows one of these four in the wreckage.
Spans: the bounce you can calculate
Joist span tables (IRC Table R507.6 in recent editions) give, for Southern pine at 16 inches on center and a 40 psf live load: a 2×8 spans about 11 ft 10 in., a 2×10 about 14 ft, a 2×12 about 16 ft 6 in. — exact figures depend on species, grade and edition, so treat these as planning numbers. Two practical consequences: a 14-foot-deep deck on 2×8 joists is over-spanned before it is built, and composite decking — less stiff underfoot than wood — makes marginal spans feel worse, which is why most composite manufacturers want 16 inches on center maximum and 12 inches for diagonal or picture-frame-heavy layouts. Cantilevers are limited (commonly to one-quarter of the adjacent span), and beams follow their own span table based on how much joist length they carry.
Lateral load: the connection nobody sees
Decks want to sway and to pull away. Modern code requires lateral-load devices — tension ties rated at 750 lbs each (two per deck) or a 1,500-lb hold-down pattern in older editions — tying deck joists back to the house floor system. Freestanding decks avoid the ledger entirely but must be braced in both directions instead. Either way, “the deck felt solid when we jumped on it” is not a lateral system.
Fastener corrosion: ACQ changed the rules
Modern pressure treatment (ACQ, CA and their successors) is substantially more corrosive to steel than the CCA it replaced. The working rules: hot-dip galvanized (ASTM A153) or stainless fasteners and connectors in all treated lumber; stainless — not galvanized — in coastal salt air and with some tropical hardwoods; never plain electro-galvanized “deck screws” in structural connections; and never mix metals casually (an aluminium flashing against ACQ-treated wood corrodes the aluminium). Joist hangers, post bases and ledger flashing should all be rated for treated-wood contact — look for G185 or ZMAX-class coatings at minimum.
Inspecting an existing deck? Probe the ledger area and the house rim from inside the basement if you can; softness there outranks every surface symptom. Check for joist hangers with the wrong nails (short roofing nails in hanger holes are a recurring find), and look at post-to-beam connections — a beam merely bolted to the side of a post, carrying load in bolt shear alone, is an older detail modern code has replaced with bearing on the post or a rated connector.